Important, 2) setting output, Example: change the pulse output to alarm output – Yokogawa digitalYEWFLO (DY) User Manual

Page 60

Advertising
background image

<7. OPERATION FOR THE BRAIN TERMINAL (BT200)>

7-4

IM 01F06A00-01EN

(2) Setting Output

Example: Change the pulse output to alarm output

F0705.ai

Enter menu item, and press
“ ” key.
Move the inverse video bar
to “B : EASY SETUP”.

Item B menu is displayed.

Move the inverse video bar
to “B20 : CONTACT OUT”.

Pressing “ENTER”, cause
the data setup screen to be
displayed.

If the security screen
appears,
enter the security code.

Move the inverse video bar
to “ALARM”.

2 Times

4 Times

Pressing the enter key,
inverse video bar is flashed.

The data setting can be
completed.

If data setting is missing,
press “F3” key and rewrite
the data.

Setting is completed.
The screen returns to the
preceding screen when the
F4” (ESC) key is pressed.

MENU

A:DISPLAY

B:EASY SETUP

C:BASIC SETUP

D:AUX. SETUP

E:METER SETUP

H:ADJUST
HOME SET ADJ ESC

PARAM

B10:FLOW SPAN

100 m3/h

B15:DAMPING

4 sec

B20:CONTACT OUT

SCALED PULSE
DATA DIAG PRNT ESC

PARAM

B10:FLOW SPAN

100 m3/h

B15:DAMPING

4 sec

B20:CONTACT OUT

SCALED PULSE
DATA DIAG PRNT ESC

PARAM

B10:FLOW SPAN

100 m3/h

B15:DAMPING

4 sec

B20:CONTACT OUT

ALARM
DATA DIAG PRNT ESC

SET

B20:CONTACT OUT

SCALED PULSE

< OFF >

< SCALED PULSE >

<UNSCALED PULSE>


ESC

SET

B20:CONTACT OUT

SCALED PULSE

<UNSCALED PULSE>

< FREQUENCY >

< ALARM >


ESC

SET

B20:CONTACT OUT

SCALED PULSE

ALARM

Print off

F2:printer on
FEED POFF NO

SET

B20:CONTACT OUT

ALARM


FEED NO OK

IMPORTANT

After setting a parameter, keep the power on for
at least 30 seconds.
If the power of fl owmeter is turned off, a
parameter setting is released.