<14. EXPLOSION PROTECTED TYPE INSTRUMENT>

14-5

IM 01F06A00-01EN

• Intrinsically

Safe

Applicable Standard: FM3600 1998, FM3610 2010,

FM3611 2004, FM3810 2005,

NEMA 250 1991,

ANSI/ISA-60079-0:

2009,

ANSI/ISA-60079-11:

2009

Type of Protection: Intrinsically safe for Class I, II,

III, Div.1, Groups A, B, C, D, E,
F and G,T4 and Class I, Zone
0, AEx ia IIC T4 Nonincendive
for Class I, II, Div. 2, Groups A,
B, C, D, F and G, Class III,Div.1,
T4, and Class I, Zone 2, Group
IIC, T4

Ambient Temperature: –29 to +60°C

(Integral Type Vortex
Flowmeter)

–29 to +80°C

(Remote Type Vortex Flow
Detector)

–40 to +60°C

(Remote Type Vortex Flow
Converter)

Indoors and Outdoors: Type 4X
Electrical Parameters: Vmax=30Vdc,

Imax=165mAdc,

Pi=0.9W, Ci=12nF,
Li=0.15mH

Electrical connection : ANSI 1/2 NPT female

(2) Wiring

• Explosion

proof

WARNING

• All wiring shall comply with National

Electrical Code ANSI/NFPA 70 and Local
Electrical Code.

• “SEAL ALL CONDUITS 18 INCHES” "

WHEN INSTALLED DIV.2, SEALS NOT
REQUIRED".

• Intrinsically

Safe

NOTE

• The FM Approved Hand Held Communicator

may be connected at any point in the loop
between the digitalYEWFLO and the Control
Equipment.

(3) Operation

• Explosion

proof

WARNING

• Note a warning label worded as follows.
Warning:

OPEN CIRCUIT BEFORE
REMOVING COVER.
INSTALL IN ACCORDANCE WITH
THE INSTRUCTION MANUAL (IM)
IF6A1-01E.

• Take care not to generate mechanical

spark when access to the instrument and
peripheral devices in hazardous locations.

(4) Maintenance and Repair

WARNING

• The instrument modifi cation or part

replacements by other than authorized
representative of Yokogawa Electric
Corporation is prohibited and will void the
approval of FM Approvals.