3 event notification, 3 event, Notifi cation -7 – Yokogawa digitalYEWFLO (DY) User Manual

Page 79: E. burst mode, 3 event notifi cation, 1) set event notifi cation, A) event mask, C) event notifi cation control, 2) acknowledge event notifi cation (dtm), A) get event number

Advertising
background image

<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>

9-7

IM 01F06A00-01EN

e. Burst Mode

When the Burst mode is set to Wired HART
Enabled, the device starts to send the data.

• Procedure to call up the display

[Root Menu]

→ Detailed setup → Confi gure

outputs

→ HART output → Burst condition → Burst

Message1, 2 or 3

→ Burst mode → Wired HART

Enabled

9.10.3 Event Notifi cation

When a setting change and a change of the Self-
diagnostics occur, device detect it as an event and
can transmit an alarm signal continuously.
Alarm contained in the following item can be set to
Event, and can be detected.

• Device

Status

• Status group 1 to 3
• Ext dev status
• Device diagnostic status 0

Up to four events that occurred can be stored.
When using this function, set to Burst mode as
“Wired HART Enabled”.

(1) Set Event Notifi cation

• Procedure to call up the display

DD (HART 7)
DTM (HART 7)

[Root Menu]

→ Detailed setup →

Confi gure outputs

→ HART output →

Event Notifi cation

→ Event

Notifi cation
Control

Stop the event monitor: OFF
Shift to the monitor state:
Enable event notifi cation on token-
passing data
link layer

→ Event Mask

Set the status to detect

→ Event

Notifi cation
Retry Time

Set the retry time when the event occur.

→ Max Update

Time

Set the retry time when the event does
not occur.

→ Event Debounce

Interval

The setting of the minimum event
duration

a) Event Mask

Set the status to detect in the Event Mask
parameter.

Device Status Mask
Status group 1 to 3
Ext dev status Mask
Device Diagnostic Status 0 Mask

b)

Event Notifi cation Retry Time/ Max
Update Time/ Event Debounce Interval

Set to Event Notifi cation Retry Time, Max
Update Time and Event Debounce Interval.
For Event Noteifi cation Retry Time, set the
value thet is smaller than Max Update Time.

Event Notifi cation Retry

Time/Max Update Time

Event Debounce Interval

Off

0.5 s

0.5 s

1 s

1 s

2 s

2 s

4 s

4 s

8 s

8 s

16 s

16 s

32 s

32 s

1 min

1 min

5 min

5 min

10 min

10 min

15 min

15 min

30 min

30 min

45 min

45 min

60 min

60 min

c) Event Notifi cation Control

Select “Enable event notifi cation on token-passing
data link layer” in the Event Notifi cation Control
parameter to shift to the monitor state:

(2) Acknowledge Event Notifi cation (DTM)

The transmission of the event message stops
when event is approved.

• Procedure to call up the display

DTM (HART 7)

[Root Menu]

→ Detailed setup →

Confi gure outputs

→ HART output →

Event Notifi cation

→ Knowledge →

→ Acknowledge

Event
Notifi cation

Acquisition of the event number and
approval.

a) Get Event Number

Confi rm the latest event number.
Execute Acknowledge Event Notifi cation
method.

1) Set “0” to enter Event Number.
2) OK.
3) Set “Trans 0: Read Event Notifi cation” to

Select Transaction.

4) OK.
5) Confi rm Event Number.

Advertising