<7. OPERATION FOR THE BRAIN TERMINAL (BT200)>

7-1

IM 01F06A00-01EN

7.

OPERATION FOR THE BRAIN

TERMINAL (BT200)

This chapter describes the operation procedures
using a BRAIN TERMINAL (BT200). For details
on the functions of the digitalYEWFLO, refer to
Chapter 6 “PARAMETERS.” List. And also, refer to
the “Model BT200 BRAIN TERMINAL” Instruction
Manual (IM 01C00A11-01E) for more detailed
Information.

7.1 Connection Method for the

BT200

(1) Connecting the BT200 to a 4 to 20mA

DC Transfer Line

The communication signal of the

digitalYEWFLO is superimposed onto the 4 to
20mA DC analog signal to be transferred.

digitalYEWFLO

SUPPLY

BT200

BT200

BT200

BT200

Inter mediate
terminals

4 to 20mA DC
Signal
transmission
line

Control room

Receiving
instrument
load
resistance:
WRŸ

Terminal

Board

SUPPLY

F0701.ai

Figure 7.1

Communicating for a 4 to 20mA DC

Signal Line

IMPORTANT

The communicable distance of the transmission
line is restricted depending on the wiring method.
Refer to Chapter 4 “WIRING.”

IMPORTANT

After setting a parameter, keep the power on for
at least 30 seconds.
If the power of fl owmeter is turned off, a
parameter setting is released.

(2) Connection of BT200 to Flow Converter

Removing a cover and indicator, the terminals

for BRAIN communication are provided on the
circuit board.

Connect BT200 to the terminal of HHT-COM on

the circuit board.

TP2

COM

HHT

P

F0702.ai

BT200

Display

Indicator Mounting
Screw (2 PCS)

Circuit board

Figure 7.2

Connection of BT200 to Flow Converter