2 selection of wires, 3 connection, Selection of wires -2 – Yokogawa digitalYEWFLO (DY) User Manual

Page 21: Important

Advertising
background image

<4. WIRING>

4-2

IM 01F06A00-01EN

R=

E–10.5
0.0236

250

600

10.5

16.4

24.7

30

42

Power Supply Voltage E (V)

Communication

Applicable range

BRAIN and HART

Load resistance R (

Ÿ

)

F0401.ai

Figure 4.1

Relationship between Power Supply

Voltage and Load Resistance (4 to 20

mA DC Output)

(2) Pulse output and Alarm, Status Output

This version uses three wires between the
converter and the power supply. A DC power
and load resistance are required, and pulse
output is connected to a totalizer or an electric
counter. Low level of the pulse output is 0
to 2V. No communication is possible over
a transmission line. Communication via the
amplifi er board is always possible irrespective
of the wiring condition.

(3) Simultaneous Analog-Pulse Output

When using digitalYEWFLO in the
simultaneous analog -pulse output mode, the
communicable distance of the transmission
line is restricted on the wiring method. Table
4.1 shows the examples of connection for this
output mode. Communication via the amplifi er
board is always possible irrespective of the
wiring condition.

IMPORTANT

For pulse output and the simultaneous analog-
pulse output ,use the load resistance. Refer to
Table 4.1.

4.2 Selection of Wires

The following should be taken into consideration
when selecting cables for use between the
converter and distributor.
(1) Use 600V PVC insulated wire or equivalent

standard wire or cable.

(2) Use shielded wire in areas susceptible to

electrical noise (both analog and pulse output
versions).

(3) In areas with high or low ambient temperatures,

use wires or cables suitable for such
temperatures.

(4) In atmospheres where oils or solvents,

corrosive gases or liquids may be present, use
suitable wires or cables.

(5) Use cable which withstand temperature up to

+60°C and more, when ambient temperature is
more than +60°C.

IMPORTANT

For the remote type, use DYC signal cable
to connect the converter and remote type
fl owmeter(DY-N).

4.3 Connection

Table 4.1 shows the connection sample of
connection for power supply and load resistance.
The terminal position of each connection is shown
in Figure 4.2.

Integral type

Remote type

F0402.ai

4 to 20 mA DC Output Power Supply
and Output Signal Terminals

Supply

+

Pulse Output Terminal

Pulse

+

Grounding Terminal

Figure 4.2

Terminal Position