background image

<Toc> <Ind>

< 6. Modbus/TCP Communication Protocol>

6-11

IM 77C01E01-10E

6.4.4

Response Error Codes

When a response is returned

If an inconsistency is found in a request’s PDU, the PR300 ignores the request and returns
the following response.

Element

Number of bytes

Command

element

Hex value

MBAP Header

2

2

2

1

1

1

Arbitrary

0000

03

01 to 99

PDU

Unit ID

Function

code

Transaction ID

Protocol ID

Error
code

Number of

bytes

*The function code entered here is the request’s function code (in hex) plus 80 (in hex).

Response Error Codes

Meaning

Funcation code error

Abnormal number of D registers

Error Code

01

03

02

Abnormal D register number

Cause

Function code does not exist.

Number of D registers out of the range is specified.

D register number out of the range is specified.

When a response is not returned

In the following cases, the PR300 ignores the request and does not return a response.

When no connection is established at the TCP/IP socket interface.

When an inconsistency is found in a request’s MBAP header.

When the communication with the serial communication device specified in Unit ID is
unusual.

Note: As a measure against the abovementioned problems, add a time-out process to the communication function or

program of the higher-level device.