3.5.9

Default Gateway (for Ethernet communication)

[Procedure]

(1)

To set the default gateway, write data to the four D registers in the table below. The
data type is integer.

(2)

After writing that value, write 1 to the Ethernet writing status register, D0294.

D Register

D0289
D0290
D0291
D0292

D0294

Reference No.

40289
40290
40291
40292

40294

H No.

0120
0121
0122
0123

0125

Description

Default gateway-1 (DG-1)
Default gateway-2 (DG-2)
Default gateway-3 (DG-3)
Default gateway-4 (DG-4)

Ethernet writing status
(D0281 to D0293 are
validated)

Effective Range

0 to 255
0 to 255
0 to 255
0 to 255

If other than 1: Invalid
If 1: Writing is executed

Initial value of default gateway: 0.0.0.0

Default Gateway

DG-1

0 to 255

DG-2

0 to 255

DG-3

0 to 255

DG-4

0 to 255

NOTE

A default gateway value can be set for the PR300 with Ethernet communication
function.

Default gateway settings are only effective when the protocol is set to Modbus/TCP.

[Example]

To set the default gateway to 0. 0. 0. 0:

For station number 01, use PC link communication (without checksum) and the random
write command as shown below:

[Command]

[STX]01010WRW05D0289,0000,D0290,0000,D0291,0000,D0292,0000,D0294,0001[ETX][CR]

[Response]

[STX]0101OK[ETX][CR]