5-10

<Toc> <Ind>

<5. Modbus/RTU and ASCII Communication Protocols>

IM 77C01E01-10E

5.2

Message and Response

Function codes are command words used by the higher-level device to obtain the D
registers information of PR300.

Table 5.3 Function Codes

Code

Function

Description

03

06

08

16

Reads data from multiple D registers.

Writes data into D register.

Performs loop back test.

Writes data into multiple D registers.

Capable of reading data from a maximum of 64 successive
D registers between D0001 and D0400.

Capable of writing data into one D register between D0001
and D0400.

Used when checking communication wiring.

Capable of writing data into a maximum of 32 successive
registers between D0001 and D0400.

The write function codes cannot be written into read-only or user-prohibited D regis-
ters.

Broadcast addressing is possible with function codes 06 and 16 only. (Also in this
case, cannot be written into read-only or user-prohibited D registers.)