4 specifying broadcast, Specifying broadcast -5 – Yokogawa PR300 Power and Energy Meter User Manual

Page 66

Advertising
background image

<Toc> <Ind>

<4. PC Link Communication Protocol>

4-5

IM 77C01E01-10E

4.1.4

Specifying Broadcast

The corresponding multiple PR300 perform the function to receive and process a com-
mand in which this station number is specified.

(1)

Specify “P1” for the station number in the command to execute it.

(2)

This command works independently of station numbers of slave stations (01 to 99).

(3)

This command is applicable for writing only.

(4)

No response is returned from the PR300 when communication is performed using this
command.

PC

RS-485 communication

Maximum communication distance: 1200 m
Maximum number of slave stations to be connected: 31

Broadcast data.

* No response from slave stations

Figure 4.2 Broadcasting

[Example of Starting Optional Integrations]

Use PC link communication (without checksum) and the random write command as shown
below:

[STX]P1010WRW01D0302,0000[ETX][CR]

D Register

D0302

Reference No.

40302

H No.

012D

Description

Optional integration start/stop
(D0011 to D0014)

Effective Range

0: Stop
1: Start