IM 77C01E01-10E

3.7.2

Maximum/Minimum Values Reset

[Procedure]

(1)

To execute maximum/minimum values reset, write data to the D register in the table
below. The data type is integer.

D Register

D0351

Reference No.

40351

H No.

015E

Description

Maximum/minimum values
(D0101 to D0138) reset

Effective Range

If other than 1: Invalid
If 1: Maximum/minimum
values reset

[Example]

To execute maximum/minimum values reset:

For station number 01, use PC link communication (without checksum) and the random
write command as shown below:

[Command]

[STX]01010WRW01D0351,0001[ETX][CR]

[Response]

[STX]0101OK[ETX][CR]

3.7.3

Energy Value All-Reset

[Procedure]

(1)

To execute energy value all-reset, write data to the D register in the table below. The
data type is integer.

D Register

D0352

Reference No.

40352

H No.

015F

Description

Energy value all-reset

Relevant items are as follows:
Active energy (D0001, D0002)
Regenerative energy (D0003, D0004)
LEAD reactive energy (D0005, D0006)
LAG reactive energy (D0007, D0008)
Apparent energy (D0009, D0010)

Effective Range

If other than 1: Invalid
If 1: Energy value all-reset

[Example]

To execute energy value all-reset:

For station number 01, use PC link communication (without checksum) and the random
write command as shown below:

[Command]

[STX]01010WRW01D0352,0001[ETX][CR]

[Response]

[STX]0101OK[ETX][CR]