Communications overview, 1 rs-485 communication specifications, 2 ethernet communication specifications – Yokogawa PR300 Power and Energy Meter User Manual

Page 9: Rs-485 communication specifications -1, Ethernet communication specifications -1

Advertising
background image

<Toc> <Ind>

<1. Communications Overview >

1-1

IM 77C01E01-10E

1.

Communications Overview

1.1

RS-485 Communication Specifications

Protocols available for RS-485 communication interfaces include the PC link com-
munication protocol and the Modbus communication protocol.

Table 1.1 RS-485 Communication Specifications

Communication Hardware

Item

Details Connected

Device

2-wire system RS-485

PR201 original communication

Personal computer etc. with SCADA
software installed to support PR201
original communication protocol

Compliant Standard
Protocol Specification

EIA RS-485
PC Link Communication with
and without checksum

Modbus Communication
(ASCII and RTU modes)

A PC installed with a driver for PC link
communication and SCADA software,
PLC (FA-M3 UT link module), etc.

A PC installed with a Modbus driver
and SCADA software,
a Modbus-compatible PLC, etc.

2400 bps, 9600 bps, 19200 bps
1200 m

31

2-wire, half-duplex
Start-stop synchronization
Non-procedural
Shielded twisted pair cable
(AWG24-equivalent size)

Baud Rate
Maximum Communication Distance
Maximum Number of
Connectable Devices
Transmission Method
Synchronization
Communication Method
Communication Cable

1.2

Ethernet Communication Specifications

Protocols available for Ethernet communication interfaces include the Modbus/TCP
communication protocol.

Table 1.2 Ethernet Communication Specifications

Communication Hardware
Compliant Standard
Access Control
Protocol Specification
Baud Rate
Maximum Segment Length
Maximum Connecting
Configuration
Communication System
Data Format
Maximum Number of
Connections

Item

Details

10BASE-T/100BASE-TX
Ethernet IEEE802.3
CSMA/CD
Modbus communication (Port No.: 502)
10 Mbps/100 Mbps
100 m *1
Cascade max. 4 levels (for 10BASE-T)
max. 2 levels (for 100BASE-TX) *2
TCP/IP
Binary
1

Connected Device

Ethernet-equipped PC etc.

*1: Distance between the hub and module.
*2: The number of hubs connectable in cascade configuration.

Advertising