<5. Modbus/RTU and ASCII Communication Protocols>

5-13

IM 77C01E01-10E

08

Performs loop back test

Function

This function code is used to check connection for communication.

For the format of response in the event of failure, see subsection 5.1.4.

The “00” shown below (marked with an asterisk *) are fixed.

Any value can be selected for transmit data.

Message (for normal operation)

Element

Number of bytes

in RTU mode

Number of bytes

in ASCII mode

Start of

Message

Mark (:)

None

1

Error

Check

2

2

Station

Number
(ST-NO)

1

2

None

End of Message Mark

(CR + LF)

2

Function Code

(08)

1

2

00

0000

2

4

4

2

Transmit Data

(Arbitrary)

Message (continued)

Response (for normal operation)

Element

Number of bytes

in RTU mode

Number of bytes

in ASCII mode

Start of

Message

Mark (:)

None

1

Error

Check

2

2

Station

Number
(ST-NO)

1

2

None

End of Message Mark

(CR + LF)

2

Function Code

(08)

1

2

00

0000

2

4

4

2

Same as

Transmit Data

Response (continued)

Diagnostic Codes

Meaning

Command message return

Diagnostic Code

0000

Data

Arbitrary

Example (ASCII mode)

Send data 0000 (fixed) and transmit data 04D2 (arbitrary) to the station number 11 to check
the connection for communication.

[Message]

[:]0B08000004D217[CR][LF]

When the connection is normal, the following response same as the command will be
returned.
[Response]

[:]0B08000004D217[CR][LF]