<7. Functions and Usage of D Registers>

7-1

IM 77C01E01-10E

7.

Functions and Usage of D Registers

7.1

Overview of D Registers

This section describes the functions and usage of D registers.

The D registers store the input values, statuses, and others that are handled by the
PR300. By connecting the PR300 to higher-level device capable of PC link commu-
nication, Modbus communication, or Ethernet communication, you can readily use
these internal data items by reading from or writing to the D registers.

7.2

Configuration of D Registers

Description

D0001 to D0100

Process data (measurement data)

Electric energy, instantaneous value and status

D0101 to D0200

Process data (statistics data)

Maximum value and minimum value

D0201 to D0300

Parameter data

Setup conditions such as VT ratio and CT ratio

D0301 to D0400

Control data

Control of operations such as remote reset

Register No.

Classification

Cannot be used. Writing to this area is not guaranteed.

Prohibited area (blank)

Other

7.3

Interpretation of D Register Map Table

This section explains how to read the D Register Map tables in this chapter. The
numbers listed in the leftmost column are D register numbers ((1) below). The five-
digit numbers in the next column are reference numbers used for Modbus communi-
cation ((2) below). The numbers in the column third from left are register numbers in
hexadecimal used in Modbus communication programs ((3) below).

H No.

Register

Symbol

Register Name

Effective Range

Initial
Value

Back-

up

R/W

D-Reg

No.

Ref
No.

0 to 99,999,999 [kWh]

(1) D register number

(2) Reference number (for Modbus communication)

(3) Hex number (for Modbus communication)

Register symbol

Register name

Effective (setting) range and unit

Initial value

Backup of data

Backed up at instantaneous

power failure

Backed up at setting

With no backup

Permission of read/write by communcation

R: Read/W: Write

An asterisk (*) in this column

indicates that the number of writing

action is limited to 100,000 times.

D0001

40001

0000

kWh L

Active energy (uint32, lower 2 bytes)

R

D0002

40002

0001

kWh H

Active energy (uint32, upper 2 bytes)

Data Format Abbreviations

float: single precision floating decimal point

uint: without sign integer

int:

with sign integer