2.1.1

Procedure for RS-485 Communication

Communication parameters setting for PR300
Set up the communication function using
the front panel keys.

Subsection 2.2.1 “Conditions for RS-485
Communication”

Higher-level device

Station number 01

(arbitrary)

Station number 02

(arbitrary)

Station number 10

(arbitrary)

Station number 20

(arbitrary)

Maximum communication distance: 1200 m
Maximum number of slave stations to be connected: 31

(Example)

See

Connect a higher-level device with PR300

Subsection 2.3.1
“Wiring for RS-485 Communication”

See

Create communication programs for the
higher-level device to perform
communication

Chapter 3
“Procedures for Setting PR300 Functions”

For communication protocol, see
Chapter 4
“PC Link Communication Protocol”
Chapter 5
“Modbus/RTU and ASCII Communication Protocols”
Chapter 8
“PR201 Original Communication Protocol”

For data storage location, see
Chapter 7
“Functions and Usage of D Registers”