4 active energy reset, 5 regenerative energy reset, Active energy reset -33 – Yokogawa PR300 Power and Energy Meter User Manual

Page 56: Regenerative energy reset -33

Advertising
background image

<Toc> <Ind>

<3. Procedures for Setting PR300 Functions>

3-33

IM 77C01E01-10E

3.7.4

Active Energy Reset

[Procedure]

(1)

To execute active energy reset, write data to the D register in the table below. The
data type is integer.

D Register

D0353

Reference No.

40353

H No.

0160

Description

Active energy
(D0001 and D0002) reset

Effective Range

If other than 1: Invalid
If 1: Active energy reset

[Example]

To execute active energy reset:

For station number 01, use PC link communication (without checksum) and the random
write command as shown below:

[Command]

[STX] 01010WRW01D0353, 0001 [ETX] [CR]

[Response]

[STX] 0101OK [ETX] [CR]

3.7.5

Regenerative Energy Reset

[Procedure]

(1)

To execute regenerative energy reset, write data to the D register in the table below.
The data type is integer.

D Register

D0354

Reference No.

40354

H No.

0161

Description

Regenerative energy
(D0003 and D0004) reset

Effective Range

If other than 1: Invalid
If 1: Regenerative energy
reset

[Example]

To execute regenerative energy reset:

For station number 01, use PC link communication (without checksum) and the random
write command as shown below:

[Command]

[STX] 01010WRW01D0354, 0001 [ETX] [CR]

[Response]

[STX] 0101OK [ETX] [CR]

Advertising