IM 77C01E01-10E

2.3

Wiring for Communication

Connect a higher-level device with the PR300 for using the communication func-
tions. The wiring procedures and precautionary notes are as follows.

2.3.1

Wiring for RS-485 Communication

For a common PC, the RS-485 interface is not directly connectable. Use a ML2 RS232C/
RS485 converter for wiring.

WARNING

To avoid an electric shock, be sure to turn off the power supply source to the equipment
involved before you start wiring.

Use crimp-on terminals at cable ends.

Before you start wiring, read the user’s manual of each device.

5

4

6

3

PR300
(with RS-485
communication function)

PR300
(with RS-485
communication function)

PC

Terminator

120

1/4W

Terminator (built-in)

120

1/4W

RS-232C
straight cable

JIS Class D (3) grounding
(grounding resistance
of 100

or less)

JIS Class D (3) grounding
(grounding resistance
of 100

or less)

Communication cable

Communication cable

A

؊

B

؉

SG

A

؊

B

؉

SG

18

19

20

17

18

19

20

Wthen terminating on
wiring, short-circuit
terminals 17 and 18 .

(RS232C/RS485 converter)

Note: Use UL Listed RS-232C/RS-485 converter if the converter has AC/DC power supply input; this is

optional for converters supplied by a Limited Power Source with input voltages less than 30 V AC or
60 V DC and which are separated from mains by double or reinforced insulation.

Communication cable: Shielded twisted pair cable (AWG24-eqivalent size)
Recommended terminals: See the PR300 Power and Energy Meter User’s Manual (electronic manual).