Parameter: g (reads electric energy) • function, Command/response, Example – Yokogawa PR300 Power and Energy Meter User Manual

Page 131

Advertising
background image

8-16

<Toc> <Ind>

<8. PR201 Original Communication Protocol>

IM 77C01E01-10E

Parameter: G (Reads electric energy)

• Function

Reads the active energy.

• Command/response

Number

of bytes

1

2

1

2

2

1

1

Command

element

STX

DG

G

Station

number

(ADR)

Checksum ETX

CR

There is no command data for data reading.

1

2

1

2

8

Response

element

STX

DG

G

Station

number

(ADR)

ٗٗٗٗٗ

E+

2

1

1

Checksum ETX

CR

Number

of bytes

Response data is returned as an 8-byte ASCII character string (00000E+0 to 99999E+6).

• Example

Reads the active energy of PR300 with station number 01.

ᮀᮀ

indicates the checksum

value.

[Command]

[STX]DGG01

ᮀᮀ

[ETX][CR]

Returns a response of the active energy: 10 MWh (10000E+3 Wh) for the above
command.

[Response]

[STX]DGG0110000E+3

ᮀᮀ

[ETX][CR]

NOTE

Display ranges of active energy vary depending on the values of the VT and CT ratios. See
the following table for display range details.

Secondary rated power

x VT ratio x CT ratio

100 kW or less

100 kW or more, 1 MW or less

1 MW or more, 10 MW or less

10 MW or more

Internal data

99999 kWh

999999 kWh

9999999 kWh

99999999 kWh

Index display

range

99999E+3 Wh

99999E+4 Wh

99999E+5 Wh

99999E+6 Wh

PR201 original communication

display range

99999 kWh

999990 kWh

9999900 kWh

99999000 kWh

NOTE

The secondary rated power of the PR300 changes depending on its model and suffix
codes.