3 demand alarm mask time, Demand alarm mask time -12 – Yokogawa PR300 Power and Energy Meter User Manual

Page 35

Advertising
background image

3-12

<Toc> <Ind>

<3. Procedures for Setting PR300 Functions>

IM 77C01E01-10E

3.4.3

Demand Alarm Mask Time

[Procedure]

(1)

Write a demand alarm mask time value to the D register in the table below. The data
type is integer.

(2)

After writing that value, write 1 to the demand measurement writing status register,
D0226.

D Register

D0220

D0226

Reference No.

40220

40226

H No.

00DB

00E1

Description

Demand alarm mask time

Demand measurement writing
status (D0218 to D0225 are
validated)

Effective Range

1 to 59
(1 to demand period)

Unit: minute

If other than 1: Invalid
If 1: Writing is executed

Initial value of demand alarm mask time: 1 minute

[Example]

To set the demand alarm mask time to 20 minutes:

For station number 01, use PC link communication (without checksum) and the random
write command as shown below:

[Command]

[STX]01010WRW02D0220,0014,D0226,0001[ETX][CR]

[Response]

[STX]0101OK[ETX][CR]

NOTE

A demand alarm mask time value can be set for the PR300 with demand measuring

function.