IM 77C01E01-10E

2.2

Setting Communication Conditions

This section describes the setting parameters for using the communication func-
tions, and the setting ranges. For details of setting method, refer to the PR300
Power and Energy Meter User’s Manual (electronic manual).

2.2.1

Conditions for RS-485 Communication

This subsection describes the setting parameters for using the RS-485 communication
function, and the setting ranges.

Table 2.1 Parameters to be Set for Communication Functions

Parameter Name

Protocol

(COMM)

(ST-NO)

(RS-485

communication)

(B-RT)

(PRI)

(STP)

(DLN)

PC link without checksum

2400 bps

9600 bps

19200 bps

1

2

7

8

(NONE)

(EVEN)

(ODD)

(PCLK1)

(PCLK2)

(M ASC)

(M RTU)

(M TCP)

(PR201)

Parameter Symbol

Menu

Setting Range

Initial

Value

Baud rate

Parity*

3

Stop bit*

3

Data length*

2

*

3

Station number

9600

NONE

1

8

01

PCLK2

PC link with checksum

Modbus/ASCII

Modbus/RTU

Modbus/TCP*

1

PR201 original

01 to 99 (01 to 31 recommended)

None

Even

Odd

*1:

Modbus/TCP can be selected for the PR300 with Ethernet communication function only.

*2:

When Modbus /RTU is selected for the protocol, select 8 for the data length. If 7 is selected for the data length,
communication is not possible.

*3:

When PR201 original is selected for the protocol, select NONE for the parity, 1 for the stop bit and 8 for the data length.