Example, Command/response – Yokogawa PR300 Power and Energy Meter User Manual

Page 125

Advertising
background image

8-10

<Toc> <Ind>

<8. PR201 Original Communication Protocol>

IM 77C01E01-10E

• Example

Reads a power factor of PR300 with station number 01.

ᮀᮀ

indicates the checksum value.

[Command]

[STX]DG601

ᮀᮀ

[ETX][CR]

Returns a response of power factor G0.8 for the above command.

[Response]

[STX]DG601G0.800

ᮀᮀ

[ETX][CR]

Parameter: 7 (Starts optional integration)

• Function

Starts optional integration.

• Command/response

Number

of bytes

1

2

1

2

2

1

1

Command

element

STX

DG

7

Station

number

(ADR)

Checksum ETX

CR

There is no command data for data reading.

1

2

1

2

0

Response

element

STX

DG

7

Station

number

(ADR)

No data

2

1

1

Checksum ETX

CR

Number

of bytes

There is no response data.

• Example

Starts optional integration of PR300 with station number 01.

ᮀᮀ

indicates the checksum

value.

[Command]

[STX]DG701

ᮀᮀ

[ETX][CR]

Returns the following response for the above command.

[Response]

[STX]DG701

ᮀᮀ

[ETX][CR]