Command/response, Example, Parameter: 3 (instantaneous power) • function – Yokogawa PR300 Power and Energy Meter User Manual

Page 122

Advertising
background image

<Toc> <Ind>

<8. PR201 Original Communication Protocol>

8-7

IM 77C01E01-10E

Parameter: 2 (Reads optional electric energy)

• Function

Reads the previous value and current value of optional electric energy.

• Command/response

Number

of bytes

1

2

1

2

2

1

1

Command

element

STX

DG

2

Station

number

(ADR)

Checksum ETX

CR

There is no command data for data reading.

1

2

1

2

5

Response

element

STX

DG

2

Station

number

(ADR)

ddddd

(Previous

value)

5

ddddd

(Current

value)

2

1

1

Checksum ETX

CR

Number

of bytes

Response data is returned as a 5-byte ASCII character string (00000 to 99999).

• Example

Reads the optional electric energy of PR300 with station number 01.

ᮀᮀ

indicates the

checksum value.

[Command]

[STX]DG201

ᮀᮀ

[ETX][CR]

Returns 10000 Wh as optional electric energy (previous value) and 10000 Wh as
optional electric energy (current value) for the above command.

[Response]

[STX]DG2011000010000

ᮀᮀ

[ETX][CR]

Parameter: 3 (Instantaneous power)

• Function

Reads the active power.

• Command/response

Number

of bytes

1

2

1

2

2

1

1

Command

element

STX

DG

3

Station

number

(ADR)

Checksum ETX

CR

There is no command data for data reading.

1

2

1

2

9

Response

element

STX

DG

3

Station

number

(ADR)

Ϯٗ

.

ٗٗٗ

E

ϩ᭺

2

1

1

Checksum ETX

CR

Number

of bytes

Response data is returned as a 9-byte ASCII character string (

±

0.000E+0 to

±

9.999E+6).