3 setting analog output, 1 selection of measurement item for analog output, Setting analog output -8 3.3.1 – Yokogawa PR300 Power and Energy Meter User Manual

Page 31: Selection of measurement item for analog output -8

Advertising
background image

3-8

<Toc> <Ind>

<3. Procedures for Setting PR300 Functions>

IM 77C01E01-10E

3.3

Setting Analog Output

3.3.1

Selection of Measurement Item for Analog Output

[Procedure]

(1)

Write a measurement item for analog output value to the D register in the table below.
The data type is integer.

(2)

After writing that value, write 1 to the analog output writing status register, D0217.

D Register

D0212

D0217

Reference No.

40212

40217

H No.

00D3

00D8

Description

Measurement item for
analog output

Analog output writing status
(D0212 to D0216 are
validated)

Effective Range

0: Active power
1: Reactive power
2: Apparent power
3: Voltage-1
4: Voltage-2
5: Voltage-3
6: Current-1
7: Current-2
8: Current-3
9: Power factor
10: Frequency

If other than 1: Invalid
If 1: Writing is executed

Initial value of measurement item for analog output: 0 (active power)

[Example]

To set the measurement item for analog output to 3 (voltage-1):

For station number 01, use PC link communication (without checksum) and the random
write command as shown below:

[Command]

[STX] 01010WRW02D0212, 0003, D0217, 0001 [ETX] [CR]

[Response]

[STX] 0101OK [ETX] [CR]

NOTE

A measurement item for analog output value can be set for the PR300 with analog
output.

Different types of the PR300 can measure different items, and so the values that can
be set to the D register differ depending on the PR300 type. If a value that cannot be
written to the D register is written, it will be invalid. The table below shows the values
that cannot be set for four types of the PR300:

Phase and Wire System

Single-phase two-wire
Single-phase three-wire
Three-phase three-wire
Three-phase four-wire (2.5 element)

Values that cannot be Set

4: Voltage-2, 5: Voltage-3, 7: Current-2, and 8: Current-3
5: Voltage-3 and 8: Current-3
4: Voltage-2 and 7: Current-2
4: Voltage-2 and 7: Current-2

When the PR300 is the three-phase four-wire system (2.5 element), the following
measurement items can be measured only when the current is in a state of equilib-
rium: “1: Reactive power”, “2: Apparent power”, “6: Current-1”, “8: Current-3” and “9:
Power factor.”