3 demand measurement start/stop, Demand measurement start/stop -37 – Yokogawa PR300 Power and Energy Meter User Manual

Page 60

Advertising
background image

<Toc> <Ind>

<3. Procedures for Setting PR300 Functions>

3-37

IM 77C01E01-10E

3.8.3

Demand Measurement Start/Stop

[Procedure]

(1)

To execute demand measurement start/stop, write data to the D register in the table
below. The data type is integer.

D Register

D0311

Reference No.

40311

H No.

0136

Description

Demand measurement start/stop

Relevant items are as follows:
Demand power (D0043, D0044)
Demand current (D0045 to D0050)

Effective Range

0: Measurement stop
1: Measurement start

Initial value of demand measurement start/stop: 0 (measurement stop)

NOTE

Demand measurement start/stop can also be controlled by operation key. Once the opera-
tion key is used, it is the only means for such control. Control via communication is not
possible until the power is turned off, or remote reset is executed (see subsection 3.7.1).

[Control via communication]

START command

STOP command

Time

Time

Perform integration for this duration

Turned on by operation key

Turned off by operation key

Data update

No response to requests
by operation key

[Control by operation key]

Turned on by operation key

Turned off by operation key

Perform integration for this duration

START

command

STOP

command

Data update

No response to requests
via communication

[Example]
To execute demand measurement start/stop:

For station number 01, use PC link communication (without checksum) and the random
write command as shown below:

<For start>
[Command]
[STX]01010WRW01D0311,0001[ETX][CR]
[Response]
[STX]0101OK[ETX][CR]
<For stop>
[Command]
[STX]01010WRW01D0311,0000[ETX][CR]
[Response]
[STX]0101OK[ETX][CR]

NOTE

Demand measurement start/stop can be performed for the PR300 with demand measuring
function.

Advertising