6 reactive energy reset, 7 apparent energy reset, Reactive energy reset -34 – Yokogawa PR300 Power and Energy Meter User Manual

Page 57: Apparent energy reset -34

Advertising
background image

3-34

<Toc> <Ind>

<3. Procedures for Setting PR300 Functions>

IM 77C01E01-10E

3.7.6

Reactive Energy Reset

[Procedure]

(1)

To execute reactive energy reset, write data to the D register in the table below. The
data type is integer.

D Register

D0355

Reference No.

40355

H No.

0162

Description

Reactive energy
(D0005 to D0008) reset

Effective Range

If other than 1: Invalid
If 1: Reactive energy
reset

[Example]

To execute reactive energy reset:

For station number 01, use PC link communication (without checksum) and the random
write command as shown below:

[Command]

[STX] 01010WRW01D0355, 0001 [ETX] [CR]

[Response]

[STX] 0101OK [ETX] [CR]

3.7.7

Apparent Energy Reset

[Procedure]

(1)

To execute apparent energy reset, write data to the D register in the table below. The
data type is integer.

D Register

D0356

Reference No.

40356

H No.

0163

Description

Apparent energy
(D0009 and D0010) reset

Effective Range

If other than 1: Invalid
If 1: Apparent energy reset

[Example]

To execute apparent energy reset:

For station number 01, use PC link communication (without checksum) and the random
write command as shown below:

[Command]

[STX] 01010WRW01D0356, 0001 [ETX] [CR]

[Response]

[STX] 0101OK [ETX] [CR]

Advertising