4 stop bit, Stop bit -19 – Yokogawa PR300 Power and Energy Meter User Manual

Page 42

Advertising
background image

<Toc> <Ind>

<3. Procedures for Setting PR300 Functions>

3-19

IM 77C01E01-10E

3.5.4

Stop Bit

[Procedure]

(1)

To set the stop bit, write data to the D register in the table below. The data type is
integer.

(2)

After writing that value, write 1 to the RS-485 writing status register, D0277.

D Register

D0274

D0277

Reference No.

40274

40277

H No.

0111

0114

Description

Stop bit

RS-485 writing status
(D0271 to D0276 are
validated)

Effective Range

1: 1 bit
2: 2 bits

If other than 1: Invalid
If 1: Writing is executed

Initial value of stop bit: 1 (1 bit)

NOTE

When Modbus/TCP is selected for the protocol, the stop bit is fixed and unchangeable at 1
bit.

[Example]

To set the stop bit to 2 (2 bits):

For station number 01, use PC link communication (without checksum) and the random
write command as shown below:

[Command]

[STX]01010WRW02D0274,0002,D0277,0001[ETX][CR]

[Response]

[STX]0101OK[ETX][CR]