3 procedure for ethernet-serial gateway function, Procedure for ethernet-serial gateway function -4 – Yokogawa PR300 Power and Energy Meter User Manual

Page 13

Advertising
background image

2-4

<Toc> <Ind>

<2. Setup>

IM 77C01E01-10E

2.1.3

Procedure for Ethernet-Serial Gateway Function

Station number 01 (fixed)
IP address [192.168.1.2] (arbitrary)

Higher-level device
IP address [192.168.1.1] (arbitrary)

Ethernet

PR300

(with Ethernet

communication function)

RS-485

Station number 02

(arbitrary)

Station number 03

(arbitrary)

Station number 20

(arbitrary)

(Example)

1

2

3

4

Communication parameters setting for PR300
Set up the communication function using
the front panel keys.

Subsection 2.2.2
“Conditions for Ethernet Communication”
Subsection 2.2.3
“Conditions for Ethernet-Serial Gateway Function”

See

Connect a higher-level device with PR300

Subsection 2.3.2
“Wiring for Ethernet Communication”

See

Connect a lower-level device with PR300

Subsection 2.3.3
“Wiring for RS-485 Communication for
Ethernet-Serial Gateway Function”

See

Create communication programs for the
higher-level device to perform
communication

Chapter 3
“Procedures for Setting PR300 Functions”

For communication protocol, see
Chapter 6
“Modbus/TCP Communication Protocol”

For data storage location, see
Chapter 7
“Functions and Usage of D Registers”

See

Note: It is recommended to use the Ethernet network as a dedicated one for the PR300.