<2. Setup>

2-3

IM 77C01E01-10E

2.1.2

Procedure for Ethernet Communication

Ethernet

LAN
connection

HUB

Station number 01 (fixed)
IP address [192.168.1.2]

(arbitrary)

Station number 01 (fixed)
IP address [192.168.1.3]

(arbitrary)

Station number 01 (fixed)
IP address [192.168.1.4]

(arbitrary)

Station number 01 (fixed)
IP address [192.168.1.5]

(arbitrary)

Maximum distance between hub and module: 100 m
Maximum number of hubs connectable in cascade configuration:

4 levels for 10BASE-T

2 levels for 100BASE-TX

1

2

3

Note: It is recommended to use the Ethernet network as a dedicated one for the

PR300.

Communication parameters setting for PR300
Set up the communication function using
the front panel keys.

Subsection 2.2.2 “Conditions for Ethernet
Communication”

Higher-level device
IP address [192.168.1.1]
(arbitrary)

(Example)

See

Connect a higher-level device with PR300

Subsection 2.3.2
“Wiring for Ethernet Communication”

See

Create communication programs for the
higher-level device to perform
communication

Chapter 3
“Procedures for Setting PR300 Functions”

For communication protocol, see
Chapter 6
“Modbus/TCP Communication Protocol”

For data storage location, see
Chapter 7
“Functions and Usage of D Registers”