<8. PR201 Original Communication Protocol>

IM 77C01E01-10E

• Example

Initializes the maximum and minimum values of PR300 with station number 01.

ᮀᮀ

indi-

cates the checksum value.

[Command]

[STX]DG901

ᮀᮀ

[ETX][CR]

Returns the following response for the above command.

[Response]

[STX]DG901

ᮀᮀ

[ETX][CR]

Parameter: A (Reads measured value and maximum/minimum values in
batch)

• Function

Reads the active energy, optional electric energy (previous and current values), active
power, voltage-1, current-1, power factor, maximum voltage-1, minimum voltage-1 and
maximum current-1.

• Command/response

Number

of bytes

1

2

1

2

2

1

1

Command

element

STX

DG

A

Station

number

(ADR)

Checksum ETX

CR

There is no command data for data reading.

1

2

1

2

5

5

5

Response

element

STX

DG

A

Station

number

(ADR)

ٗٗٗٗٗ

(Active energy)

9

Ϯٗ

.

ٗٗٗ

E

ϩ᭺

(Active power)

ddddd

(Previous value

of optional

electric energy)

ddddd

(Current value

of optional

electric energy)

Number

of bytes

Response data is returned as a 70-byte ASCII character string.

Continued

8

8

ٗ

.

ٗٗٗ

E

ϩ᭺

(Voltage-1)

ٗ

.

ٗٗٗ

E

ϩ᭺

(Current-1)

6

᭝ٗ

.

ٗٗٗ

(Power factor)

8

ٗ

.

ٗٗٗ

E

ϩ᭺

(Maximum voltage-1)

8

ٗ

.

ٗٗٗ

E

ϩ᭺

(Minimum voltage-1)

Continued

8

2

1

1

ٗ

.

ٗٗٗ

E

ϩ᭺

(Maximum current-1)

Checksum ETX

CR