<3. Procedures for Setting PR300 Functions>

3-25

IM 77C01E01-10E

3.5.10 Port Number (for Ethernet communication)

[Procedure]

(1)

To set the port number, write data to the D register in the table below. The data type is
integer.

(2)

After writing that value, write 1 to the Ethernet writing status register, D0294.

D Register

D0293

D0294

Reference No.

40293

40294

H No.

0124

0125

Description

Port number

Ethernet writing status
(D0281 to D0293 are
validated)

Effective Range

502, 1024 to 65535

If other than 1: Invalid
If 1: Writing is executed

Initial value of port number: 502

NOTE

A port number value can be set for the PR300 with Ethernet communication function.

Port number setting is only effective when the protocol is set to Modbus/TCP.

[Example]

To set the port number to 1024:

For station number 01, use PC link communication (without checksum) and the random
write command as shown below:

[Command]

[STX]01010WRW02D0293,0400,D0294,0001[ETX][CR]

[Response]

[STX]0101OK[ETX][CR]