Slave pr300 – Yokogawa PR300 Power and Energy Meter User Manual

Page 20

Advertising
background image

<Toc> <Ind>

<2. Setup>

2-11

IM 77C01E01-10E

Setting for PR300 to perform the Ethernet-serial gateway function

To use the Ethernet-serial gateway function, set the parameters of subsection 2.2.2, “Con-
ditions for Ethernet Communication” and set a parity (PRI) in Table 2.3.

When the protocol is set to Modbus/TCP, the parameters of RS-485 other than the parity
are fixed and unchangeable.

Table 2.3 Parameters of PR300 to Perform the Ethernet-Serial Gateway Function

(ST-NO)

(RS-485

communication)

(B-RT)

(PRI)

(STP)

(DLN)

01 (fixed)

9600

NONE

1

8

1 (fixed)

8 (fixed)

01

9600 bps (fixed)

NONE
EVEN
ODD

Parameter Name

Parameter Symbol

Menu

Setting Range

Initial

Value

Baud rate

Data length

Station number

None
Even
Odd

Parity

Stop bit

Slave PR300

The station number of any slave PR300 (device for RS-485 communication) must be a
different number other than 01.

The communication conditions for any slave PR300 (device for RS-485 communication)
other than the station number must conform to those in Table 2.3.

Table 2.4 Parameters of Slave PR300

(ST-NO)

(RS-485

communication)

(B-RT)

(PRI)

(STP)

(DLN)

2400 bps

9600 bps

19200 bps

1

2

7

8

NONE

EVEN

ODD

02 to 99

9600

NONE

1

8

01

Parameter Name

Parameter Symbol

Menu

Setting Range

Initial

Value

Baud rate

Data length

Station number

None

Even

Odd

Parity

Stop bit

When using the VJET Ethernet/RS-485 converter as an Ethernet-serial gateway function,
the communication conditions of any slave PR300 must conform to those of the VJET at a
higher level. The initial value of the VJET parity is EVEN.