8 subnet mask (for ethernet communication), Subnet mask (for ethernet communication) -23 – Yokogawa PR300 Power and Energy Meter User Manual

Page 46

Advertising
background image

<Toc> <Ind>

<3. Procedures for Setting PR300 Functions>

3-23

IM 77C01E01-10E

3.5.8

Subnet Mask (for Ethernet communication)

[Procedure]

(1)

To set the subnet mask, write data to the four D registers in the table below. The data
type is integer.

(2)

After writing that value, write 1 to the Ethernet writing status register, D0294.

D Register

D0285
D0286
D0287
D0288

D0294

Reference No.

40285
40286
40287
40288

40294

H No.

011C
011D
011E
011F

0125

Description

Subnet mask-1 (SM-1)
Subnet mask-2 (SM-2)
Subnet mask-3 (SM-3)
Subnet mask-4 (SM-4)

Ethernet writing status
(D0281 to D0293 are
validated)

Effective Range

0 to 255
0 to 255
0 to 255
0 to 255

If other than 1: Invalid
If 1: Writing is executed

Subnet Mask

SM-1

0 to 255

SM-2

0 to 255

SM-3

0 to 255

SM-4

0 to 255

Initial value of subnet mask: 255.255.255.0

NOTE

A subnet mask value can be set for the PR300 with Ethernet communication function.

Subnet mask settings are only effective when the protocol is set to Modbus/TCP.

[Example]

To set the subnet mask to 255. 255. 255. 0:

For station number 01, use PC link communication (without checksum) and the random
write command as shown below:

[Command]

[STX]01010WRW05D0285,00FF,D0286,00FF,D0287,00FF,D0288,0000,D0294,0001[ETX][CR]

[Response]

[STX]0101OK[ETX][CR]

Advertising