<3. Procedures for Setting PR300 Functions>

IM 77C01E01-10E

3.5.7

IP Address (for Ethernet communication)

[Procedure]

(1)

To set the IP address, write data to the four D registers in the table below. The data
type is integer.

(2)

After writing that value, write 1 to the Ethernet writing status register, D0294.

D Register

D0281
D0282
D0283
D0284

D0294

Reference No.

40281
40282
40283
40284

40294

H No.

0118
0119
011A
011B

0125

Description

IP address-1 (IP-1)
IP address-2 (IP-2)
IP address-3 (IP-3)
IP address-4 (IP-4)

Ethernet writing status
(D0281 to D0293 are
validated)

Effective Range

0 to 255
0 to 255
0 to 255
0 to 255

If other than 1: Invalid
If 1: Writing is executed

IP address

IP-1

0 to 255

IP-2

0 to 255

IP-3

0 to 255

IP-4

0 to 255

Initial value of IP address: 192.168.1.1

NOTE

An IP address value can be set for the PR300 with Ethernet communication function.

IP address settings are only effective when the protocol is set to Modbus/TCP.

[Example]

To set the IP address to 192.168.1.3:

For station number 01, use PC link communication (without checksum) and the random
write command as shown below:

[Command]

[STX]01010WRW05D0281,00C0,D0282,00A8,D0283,0001,D0284,0003,D0294,0001[ETX][CR]

[Response]

[STX]0101OK[ETX][CR]