<8. PR201 Original Communication Protocol>

8-1

IM 77C01E01-10E

8.

PR201 Original Communication Protocol

8.1

Overview

This function enables various measured values to be read into a personal computer
through the use of a command/response method. There are two ways for reading the
values. One is used to read values individually and another to read them in batch
mode (where only measurement items in the specified mode can be read).

8.2

Communication Specifications

Transmission distance

Connection method

Station number

Transmission method

Synchronization

Baud rate

Data format

Data bit

Parity

Stop bit

Xon/Xoff control

Communication error handling

PR300

Approximately 1.2 km maximum
(Use of 24 AWG twisted pair cable)

Multi-drop connection of up to 32 stations, including a high-level personal
computer

1 to 99

Half-duplex transmission

Start-stop synchronization

19200/9600/2400 bps

Start bit, one bit

8 bits

None

1 bit

Unavailable

If an invalid command is received, it is discarded and no response is returned.
Because noise or invalid commands are ignored, the higher-level PC must
perform time-out processing. The time-out time must be set to 1 second or
more. In addition, when a parameter or data causes an error, an error
response must be returned.

Command/response timing:

Command

Response

10 ms min.