<3. Procedures for Setting PR300 Functions>

3-9

IM 77C01E01-10E

3.3.2

Upper/Lower Limits of Scaling

[Procedure]

(1)

Write upper/lower limits of scaling value to the four D registers in the table below. The
data type is 4-byte floating point.

(2)

After writing that value, write 1 to the analog output writing status register, D0217.

D Register

D0213

D0217

Reference No.

40213

40217

H No.

00D4

00D8

Description

Lower limit of scaling
(float, lower 2 bytes)

D0214

40214

00D5

Lower limit of scaling
(float, upper 2 bytes)

Analog output writing status
(D0212 to D0216 are
validated)

Effective Range

0.0 to 50.0
Unit: %

D0215

40215

00D6

Upper limit of scaling
(float, lower 2 bytes)

D0216

40216

00D7

Upper limit of scaling
(float, upper 2 bytes)

50.0 to 100.0
Unit: %

If other than 1: Invalid
If 1: Writing is executed

Initial value of lower limit of scaling: 50%
Initial value of upper limit of scaling: 100%

[Example]

To set the lower limit of scaling to 10.0%:

For station number 01, use PC link communication (without checksum) and the random
write command as shown below:

If 10.0 is converted into a 4-byte floating point value, the value is 4120 0000.

[Command]

[STX] 01010WRW03D0213, 0000, D0214, 4120, D0217,0001 [ETX] [CR]

[Response]

[STX] 0101OK [ETX] [CR]

NOTE

An upper/lower limit of scaling value can be set for the PR300 with analog output.

Set an upper/lower limit of scaling so that [upper limit of scaling] – [lower limit of
scaling] is 50% or greater. If it is smaller than 50%, writing to the D register will be
invalid.