2 pulse unit, Pulse unit -6 – Yokogawa PR300 Power and Energy Meter User Manual

Page 29

Advertising
background image

3-6

<Toc> <Ind>

<3. Procedures for Setting PR300 Functions>

IM 77C01E01-10E

3.2.2

Pulse Unit

[Procedure]

(1)

Write a pulse unit value to the D register in the table below. The data type is integer.

(2)

After writing that value, write 1 to the pulse output writing status register, D0211.

D Register

D0209

D0211

Reference No.

40209

40211

H No.

00D0

00D2

Description

Pulse unit

Pulse output writing status
(D0208, D0209, and D0210
are validated)

Effective Range

1 to 50,000
Unit:

ϫ

100 Wh/pulse

If other than 1: Invalid
If 1: Writing is executed

Initial value of pulse unit: 10 (1000 Wh/pulse)

[Example]

To set the pulse unit to 100 Wh/pulse, write “0001.”

For station number 01, use PC link communication (without checksum) and the random
write command as shown below:

[Command]

[STX]01010WRW02D0209,0001,D0211,0001[ETX][CR]

[Response]

[STX]0101OK[ETX][CR]

NOTE

A pulse unit value can be set for the PR300 with pulse output.

To set the pulse unit value via communication, set it to 1/100 the value of the displayed
(true) value (e.g., set it to 5 when setting the pulse unit value to 500 Wh/pulse).