<Toc> <Ind>

<3. Procedures for Setting PR300 Functions>

IM 77C01E01-10E

3.6

Writing Energy Values

3.6.1

Active Energy

[Procedure]

(1)

Write an active energy value to the two D registers in the table below. The data type is
integer.

(2)

After writing that value, write 1 to the writing status register, D0373.

D Register

D0371

Reference No.

40371

H No.

0172

Description

Active energy-setpoint
(lower 2 bytes)

Effective Range

Refer to the "NOTE" below.

D0372

40372

0173

Active energy-setpoint
(upper 2 bytes)

D0373

40373

0174

Active energy value writing
status

If other than 1: Invalid
If 1: Writing is executed

[Example]

To set the active energy value to 10,000,000 kWh:

For station number 01, use PC link communication (without checksum) and the random
write command as shown below:

If 10,000,000 is converted into a hexadecimal value, the value is 0098 9680. Then the
order of the upper two bytes and the lower two bytes is reversed

9680 0098.

[Command]

[STX] 01010WRW03D0371, 9680, D0372, 0098, D0373, 0001 [ETX] [CR]

[Response]

[STX] 0101OK [ETX] [CR]

NOTE

The set active energy value range of the PR300 changes depending on the values of the
VT and CT ratios. The table below shows the set value range.

[Secondary Rated Power]

ϫ

[VT Ratio]

ϫ

[CT Ratio]

Less than 100 kW

100 kW to less than 1 MW

1 MW to less than 10 MW

10 MW or greater

Possible Set Value Range

0 to 99999 kWh

0 to 999999 kWh

0 to 9999999 kWh

0 to 99999999 kWh

NOTE

The secondary rated power of the PR300 changes depending on its model and suffix
codes.