<3. Procedures for Setting PR300 Functions>

3-31

IM 77C01E01-10E

3.7

Executing Reset Operations

3.7.1

Remote Reset

[Procedure]

(1)

To execute remote reset, write data to the D register in the table below. The data type
is integer.

D Register

D0400

Reference No.

40400

H No.

018F

Description

Remote reset

Effective Range

If other than 1: Invalid
If 1: PR300 reset

Initial value of remote reset: 0

NOTE

When remote reset is executed, maximum, minimum and instantaneous voltage
values and maximum and instantaneous current values will be reset. Optional integra-
tion is terminated if it is being performed.

Even when remote reset is executed, active energy, reactive energy, and apparent
energy data as well as set parameter values are retained.

[Example]

To execute remote reset:

For station number 01, use PC link communication (without checksum) and the random
write command as shown below:

[Command]

[STX] 01010WRW01D0400, 0001 [ETX] [CR]

[Response]

[STX] 0101OK [ETX] [CR]

NOTE

After remote reset is executed, wait for 10 seconds or more before sending another com-
mand. It takes about 10 seconds to reset.
Even when PR300 was reset by power supply switch off/on, also wait for 10 seconds or
more before sending another command.