3 command/response format, Command/response format -2 – Yokogawa PR300 Power and Energy Meter User Manual

Page 117

Advertising
background image

8-2

<Toc> <Ind>

<8. PR201 Original Communication Protocol>

IM 77C01E01-10E

8.3

Command/Response Format

Command components:

STX

Command Parameter

Station

number

Data

Checksum

ETX

CR

Checksum range

1 byte

2 bytes

1 byte

2 bytes

Variable-

length

2 bytes

1 byte

1 byte

STX:

Start of Text (hexadecimal: 02)

Command:

2-byte ASCII code (DG or DP)

Parameter:

1-byte ASCII code (0 to Z)

Station number:

2-byte ASCII code (01 to 63)

Data:

No data is found at data read-out time. When a setting value is
changed, a variable-length ASCII code is set (size in byte varies
depending on the parameter).

Checksum:

2-byte ASCII code (00 to FF)

This value is obtained by adding the data (hex.) in a checksum range
and converting the lower 2 digits of the resulting value.

ETX:

End of Text (hexadecimal: 03)

CR:

Carriage Return (hexadecimal: 0D)

Response components:

1 byte

2 bytes

1 byte

2 bytes

Variable-

length

2 bytes

1 byte

1 byte

STX

Response

Parameter

Station

number

Data

Checksum

ETX

CR

Checksum range

STX:

Start of Text (hexadecimal: 02)

Response:

2-byte ASCII code (DG or DP)

Parameter:

1-byte ASCII code (0 to Z)

Station number:

2-byte ASCII code (01 to 63)

Data:

Variable-length ASCII code (byte size depends on the type of param-
eter)

Checksum:

2-byte ASCII code (00 to FF)

ETX:

End of Text (hexadecimal: 03)

CR:

Carriage Return (hexadecimal: 0D)

NOTE

When a communication error occurs, the parameter Z of the DG command must be trans-
mitted to read out an error response. The details of the communication error can be deter-
mined by the contents of the error response.