<7. Functions and Usage of D Registers>

7-5

IM 77C01E01-10E

D-Reg

Ref No. H No.

Register Symbol

Register Name

Effective Range

Initial Value BackUp

R/W

No.

D0289 40289

0120

DEFAULT GATEWAY 1

Default gateway-1 (uint 32, 1 byte)

0 to 255

0

R/W

D0290 40290

0121

DEFAULT GATEWAY 2

Default gateway-2 (uint 32, 1 byte)

0 to 255

0

R/W

D0291 40291

0122

DEFAULT GATEWAY 3

Default gateway-3 (uint 32, 1 byte)

0 to 255

0

R/W

D0292 40292

0123

DEFAULT GATEWAY 4

Default gateway-4 (uint 32, 1 byte)

0 to 255

0

R/W

D0293

40293

0124 PORT NUM

Port number

502, 1024 to 65535

502

R/W

If other than 1: Invalid

D0294

40294

0125 ETHERNET STS

Ethernet writing status

If 1: Writing is executed

ϫ

W

(D0281 to D0293 are validated)

D0295 to D0300

D0301 40301

012C

INTEG START STOP

Integration start/stop

0: Stop, 1: Start

1

R/W

D0302

40302 012D Wh START STOP

Optional integration start/stop

0: Stop, 1: Start

0

ϫ

R/W

D0303 to D0310

D0311 40311

0136

DEMAND START STOP Demand measurement start/stop

0: Stop, 1: Start

0

ϫ

R/W

Confirmation and release of

0: Normal state, 1: Alarm state

D0312 40312

0137

DEMAND ALM STATUS

demand alarm state

Writing

“0” during alarm state clears

0

ϫ

R/W

the

alarm.

D0313 to D0350

If other than 1: Invalid

D0351

40351 015E MAX RST

Maximum/minimum values reset

If 1: Maximum/minimum values

ϫ

W

are reset (D0101 to D0138)

If other than 1: Invalid

D0352

40352 015F Wh ALL RST

Energy value all-reset

If 1: All energy values are reset

ϫ

W

(D0001 to D0010)

If other than 1: Invalid

D0353

40353 0160

kWh RST

Active energy reset

If 1: Active energy is reset

ϫ

W

(D0001,

D0002)

If other than 1: Invalid

D0354

40354 0161

RkWh RST

Regenerative energy reset

If 1: Regenerative energy is reset

ϫ

W

(D0003,

D0004)

If other than 1: Invalid

D0355

40355 0162

kVarh RST

Reactive energy reset

If 1: Reactive energy is reset

ϫ

W

(D0005 to D0008)

If other than 1: Invalid

D0356

40356 0163

kVAh RST

Apparent energy reset

If 1: Apparent energy is reset

ϫ

W

(D0009, D0010)

D0357 to D0370

D0371

40371 0172

kWh SET L

Active energy – setpoint (uint 32, lower 2 bytes)

See subsection 3.6.1

ϫ

W

D0372 40372

0173

kWh

SET

H Active energy – setpoint (uint 32, upper 2 bytes)

If other than 1: Invalid

D0373

40373 0174

kWh STS

Active energy writing status

If 1: The values of D0371 and D0372

ϫ

W

are written as the integrated values.

D0374 40374

0175

RkWh

L

Regenerative

energy

– setpoint

(uint 32, lower 2 bytes)

See subsection 3.6.2

ϫ

W

D0375 40375

0176

RkWh

H

Regenerative

energy

– setpoint

(uint 32, upper 2 bytes)

If other than 1: Invalid

D0376

40376 0177

RkWh STS

Regenerative energy writing status

If 1: The values of D0374 and D0375

ϫ

W

are written as the integrated values.

D0377 40377

0178

Lead kVarh SET L LEAD

reactive

energy

– setpoint

(uint 32, lower 2 bytes)

See subsection 3.6.3

ϫ

W

D0378 40378

0179

Lead kVarh SET H

LEAD reactive energy – setpoint

(uint 32, upper 2 bytes)

D0379 40379

017A

Lag kVarh SET L

LAG reactive energy – setpoint

(uint 32, lower 2 bytes)

See subsection 3.6.4

ϫ

W

D0380 40380

017B

Lag kVarh SET H

LAG reactive energy – setpoint

(uint 32, upper 2 bytes)

If other than 1: Invalid

D0381

40381 017C kVarh STS

Reactive energy writing status

If 1: The values of D0377 to D0380

ϫ

W

are written as the integrated values.

D0382

40382 017D kVAh SET L

Apparent energy – setpoint

(uint 32, lower 2 bytes)

See subsection 3.6.5

ϫ

W

D0383

40383 017E kVAh SET H

Apparent energy – setpoint

(uint 32, upper 2 bytes)

If other than 1: Invalid

D0384

40384 017F kVAh STS

Apparent energy writing status

If 1: The values of D0382 and D0383

ϫ

W

are written as the integrated values.

D0385 to D0399

If other than 1: Invalid

D0400

40400 018F RMT RST

Remote reset

If 1: PR300 is reset (the same effect

0

ϫ

W

as turning the power off and then on)

* D register with a blank cannot be used. (Writing to this area is not guaranteed.)