<3. Procedures for Setting PR300 Functions>

3-27

IM 77C01E01-10E

3.6.2

Regenerative Energy

[Procedure]

(1)

Write a regenerative energy value to the two D registers in the table below. The data
type is integer.

(2)

After writing that value, write 1 to the writing status register, D0376.

D Register

D0374

Reference No.

40374

H No.

0175

Description

Regenerative energy-setpoint
(lower 2 bytes)

Effective Range

Refer to the "NOTE" below.

D0375

40375

0176

Regenerative energy-setpoint
(upper 2 bytes)

D0376

40376

0177

Regenerative energy writig
status

If other than 1: Invalid
If 1: Writing is executed

[Example]

To set the regenerative energy value to 10,000,000 kWh:

For station number 01, use PC link communication (without checksum) and the random
write command as shown below:

If 10,000,000 is converted into a hexadecimal value, the value is 0098 9680. Then the
order of the upper two bytes and the lower two bytes is reversed

9680 0098.

[Command]

[STX] 01010WRW03D0374, 9680, D0375, 0098, D0376, 0001 [ETX] [CR]

[Response]

[STX] 0101OK [ETX] [CR]

NOTE

The set regenerative energy value range of the PR300 changes depending on the values
of the VT and CT ratios. The table below shows the set value range.

[Secondary Rated Power]

ϫ

[VT Ratio]

ϫ

[CT Ratio]

Less than 100 kW

100 kW to less than 1 MW

1 MW to less than 10 MW

10 MW or greater

Possible Set Value Range

0 to 99999 kWh

0 to 999999 kWh

0 to 9999999 kWh

0 to 99999999 kWh

NOTE

The secondary rated power of the PR300 changes depending on its model and suffix
codes.