<3. Procedures for Setting PR300 Functions>

IM 77C01E01-10E

3.8.4

Confirmation and Release of Demand Alarm State

[Procedure]

(1)

To execute confirmation and release of demand alarm state, write data to the D
register in the table below. The data type is integer.

D Register

D0312

Reference No.

40312

H No.

0137

Description

Confirmation and release
of demand alarm state

Effective Range

0: Normal state
1: Alarm state
Writing “0” during alarm state
clears the alarm

[Example]

To execute confirmation of demand alarm state:

For station number 01, use PC link communication (without checksum) and the word-basis
read (write) command as shown below:

<For read>

[Command]

[STX]01010WRDD0312,01[ETX][CR]

[Response]

[STX]0101OK0001[ETX][CR]

<For write>

[Command]

[STX]01010WWRD0312,01,0000[ETX][CR]

[Response]

[STX]0101OK[ETX][CR]

NOTE

Confirmation and release of demand alarm state can be set for the PR300 with demand
measuring function.