Parameter: g (integration reset) • function, Command/response, Example – Yokogawa PR300 Power and Energy Meter User Manual

Page 138

Advertising
background image

<Toc> <Ind>

<8. PR201 Original Communication Protocol>

8-23

IM 77C01E01-10E

Parameter: G (Integration reset)

• Function

Resets the active energy.

• Command/response

Number

of bytes

1

2

1

2

2

1

1

Command

element

STX

DP

G

Station

number

(ADR)

Checksum ETX

CR

Number

of bytes

1

2

1

2

2

1

1

Response

element

STX

DP

G

Station

number

(ADR)

Checksum ETX

CR

There is no response data.

• Example

Resets the active energy of PR300 with station number 01.

ᮀᮀ

indicates the checksum

value.

[Command]

[STX] DPG01

ᮀᮀ

[ETX][CR]

Returns the following response for the above command.

[Response]

[STX] DPG01

ᮀᮀ

[ETX][CR]

Resets the active energy.

Parameter: 4 (Sets VT ratio), parameter: 5 (Sets CT ratio), parameter: B (Inte-
grated low-cut power), parameter: C (Integration pulse unit), Parameter: D
(Integration pulse ON pulse width), Parameter: E (Analog output scaling “L”),
Parameter: F (Analog output scaling “H”) These parameters are not sup-
ported. Even if a command with any of these parameters is received, the
command is disabled. The command is discarded and an error response
(overranged command data error) is returned.