4 demand setting, 1 demand power/current, Demand setting -10 3.4.1 – Yokogawa PR300 Power and Energy Meter User Manual

Page 33: Demand power/current -10

Advertising
background image

3-10

<Toc> <Ind>

<3. Procedures for Setting PR300 Functions>

IM 77C01E01-10E

3.4

Demand Setting

3.4.1

Demand Power/Current

[Procedure]

(1)

Write a demand power/current value to the D register in the table below. The data type
is integer.

(2)

After writing that value, write 1 to the demand measurement writing status register,
D0226.

D Register

D0218

D0226

Reference No.

40218

40226

H No.

00D9

00E1

Description

Demand power/current

Demand measurement writing
status (D0218 to D0225 are
validated)

Effective Range

0: Active power
1: Current

If other than 1: Invalid
If 1: Writing is executed

Initial value of demand power/current: 0 (active power)

[Example]

To set the demand power/current to 1 (current):

For station number 01, use PC link communication (without checksum) and the random
write command as shown below:

[Command]

[STX] 01010WRW02D0218, 0001, D0226, 0001 [ETX] [CR]

[Response]

[STX] 0101OK [ETX] [CR]

NOTE

A demand power/current value can be set for the PR300 with demand measuring
function.

When the PR300 is the three-phase four-wire system (2.5 element), “1: Current” can
be measured only when the current is in a state of equilibrium.