<3. Procedures for Setting PR300 Functions>

3-35

IM 77C01E01-10E

3.8

Setting Control States

3.8.1

Integration Start/Stop

[Procedure]

(1)

To execute integration start/stop, write data to the D register in the table below. The
data type is integer.

D Register

D0301

Reference No.

40301

H No.

012C

Description

Integration start/stop

Relevant items are as follows:
Active energy (D0001, D0002)
Regenerative energy (D0003, D0004)
LEAD reactive energy (D0005, D0006)
LAG reactive energy (D0007, D0008)
Apparent energy (D0009, D0010)

Effective Range

0: Stop
1: Start

Initial value of integration start/stop: 1 (start)

[Example]

To execute integration start/stop:

For station number 01, use PC link communication (without checksum) and the random
write command as shown below:

<For start>

[Command]

[STX] 01010WRW01D0301, 0001 [ETX] [CR]

[Response]

[STX] 0101OK [ETX] [CR]

<For stop>

[Command]

[STX] 01010WRW01D0301, 0000 [ETX] [CR]

[Response]

[STX] 0101OK [ETX] [CR]