Parameter: a (remote reset) • function, Command/response, Example – Yokogawa PR300 Power and Energy Meter User Manual

Page 137

Advertising
background image

8-22

<Toc> <Ind>

<8. PR201 Original Communication Protocol>

IM 77C01E01-10E

Parameter: A (Remote reset)

• Function

Performs remote reset. If remote reset is performed, the maximum value, minimum value,
and instantaneous value of voltage and current are reset. If remote reset is performed at
the start of optional integration, optional integration itself stops. Even if remote reset is
performed, the data and parameter setting values of active energy remains unchanged.

• Command/response

Number

of bytes

1

2

1

2

2

1

1

Command

element

STX

DP

A

Station

number

(ADR)

Checksum ETX

CR

Number

of bytes

1

2

1

2

2

1

1

Response

element

STX

DP

A

Station

number

(ADR)

Checksum ETX

CR

There is no response data.

• Example

Performs remote reset on PR300 with station number 01.

ᮀᮀ

indicates the checksum

value.

[Command]

[STX]DPA01

ᮀᮀ

[ETX][CR]

Returns the following response for the above command.

[Response]

[STX]DPA01

ᮀᮀ

[ETX][CR]

Performs remote reset.

NOTE

Because the PR300 microcomputer is reset after remote reset takes place, wait for 5
seconds or more before transmitting the next command.