<3. Procedures for Setting PR300 Functions>

IM 77C01E01-10E

3.5.3

Parity

[Procedure]

(1)

To set the parity, write data to the D register in the table below. The data type is integer.

(2)

After writing that value, write 1 to the RS-485 writing status register, D0277.

D Register

D0273

D0277

Reference No.

40273

40277

H No.

0110

0114

Description

Parity

RS-485 writing status
(D0271 to D0276 are
validated)

Effective Range

0: NONE
1: EVEN
2: ODD

If other than 1: Invalid
If 1: Writing is executed

Initial value of parity: 0 (NONE)

[Example]

To set the parity to 1 (EVEN):

For station number 01, use PC link communication (without checksum) and the random
write command as shown below:

[Command]

[STX]01010WRW02D0273,0001,D0277,0001[ETX][CR]

[Response]

[STX]0101OK[ETX][CR]