<3. Procedures for Setting PR300 Functions>

3-5

IM 77C01E01-10E

3.2

Setting Pulse Output

3.2.1

Selection of Measurement Item for Pulse Output

[Procedure]

(1)

Write a measurement item for pulse output value to the D register in the table below.
The data type is integer.

(2)

After writing that value, write 1 to the pulse output writing status register, D0211.

D Register

D0208

D0211

Reference No.

40208

40211

H No.

00CF

00D2

Description

Measurement item for
pulse output

Pulse output writing status
(D0208, D0209, and D0210
are validated)

Effective Range

0: Active energy
1: Regenerative energy
2: LEAD reactive energy
3: LAG reactive energy
4: Apparent energy

If other than 1: Invalid
If 1: Writing is executed

Initial value of measurement item for pulse output: 0 (active energy)

[Example]

To set the measurement item for pulse output to 1 (LEAD reactive energy):

For station number 01, use PC link communication (without checksum) and the random
write command as shown below:

[Command]

[STX] 01010WRW02D0208, 0001, D0211, 0001 [ETX] [CR]

[Response]

[STX] 0101OK [ETX] [CR]

NOTE

A measurement item for pulse output value can be set for the PR300 with pulse
output.

When the PR300 is the three-phase four-wire system (2.5 element), the following
measurement items can be measured only when the current is in a state of equilib-
rium:
“2: LEAD reactive energy”, “3: LAG reactive energy” and “4: Apparent energy.”