NORDAC SK 750E Manual

104

Subject to technical amendments

BU 0750 GB-3311

Parameter

Setting value / Description / Note

Parameter set Available with option

P426

Emergency stop time

P

Always visible

0 ...100.00 s
[ 0.1 ]
or [ 1.0 ]

Braking time setting for the emergency stop function, which can be triggered by digital input, bus
control, keyboard or automatically in the case of an error.
The emergency stop time is the time for the linear frequency decrease from the set maximum
frequency (P105) to 0Hz. If an actual setpoint <100% is being used, the emergency stop time is
reduced correspondingly.

P427

Emergency stop on error

Always visible

0 ... 3
[ 0 ]

Activation of automatic emergency stop following error

0 = OFF: Automatic emergency stop following error is deactivated

1 = Mains supply failure: Automatic emergency stop following mains supply failure

2 = Error: Automatic emergency stop following fault

3 = Mains supply failure and error: Automatic emergency stop following mains supply failure

and error

P428

Automatic start

P

Always visible

0 ... 1
[ 0 ]

In the standard setting (P428 = 0

Off) the inverter requires a flank to enable (signal change from

"Low

High") at the relevant digital input.

In the setting On

1, the FI reacts to a High level. This function is only possible if the FI is controlled

using the digital inputs. (see P509).

In some cases, the FI must start up directly when the mains are switched on. For this P428 = 1

On

can be set. If the enable signal is permanently switched on, or equipped with a cable jumper, the FI
starts up immediately.