Parameter

Setting value / Description / Note

Parameter
set

Available in Option

P107

Brake reaction time

P

Always visible

0 ... 2.50 s
[ 0.00 ]

Electromagnetic brakes have a physically-dependent delayed reaction time when actuated. This can
cause a dropping of the load for lifting applications, as the brake only takes over the load after a
delay.
This reaction time can be taken into account under parameter P107 (Brake control).
Within the adjustable application time, the FI supplies the set absolute minimum frequency (P505)
and so prevents movement against the brake and load drop when stopping.
See also the parameter >Release time< P114
Note:

For the control of electromagnetic braking (especially for lifting operations) an internal
relay should be used, see  Function 1, external brake (P434/441). The minimum
absolute frequency (P505) should never be less than 2.0Hz.

Recommendation for application:
Lifting equipment with brake, without speed feedback


P114 = 0.2...0.3sec.
P107 = 0.2...0.3sec.
P201…P208 = Motor data
P434 = 1 (ext. brake)
P505 = 2...4Hz

for safe start-up
P112 = 402 (off)
P536 = 2.1 (off)
P537 = 1 (on)
P539 = 2/3 (I

SD

monitoring)


to prevent load drops
P214 = 50...100%
(precontrol)

Output
frequency

P107

Brake released

P114
or
P107, if P114 = 0

ON Signal

P505

OFF Signal

Time

Note:

If a brake release time is set (P107 / P114) the brake will only be actuated if at
least ¼ of the rated magnetisation current (P209) is flowing. The static boost
P120 is correspondingly taken into account with values < 100%.