4 electrical data for ul/cul certification – NORD Drivesystems BU0750 User Manual
Page 141
9 Technical data
BU 0750 GB-3311
Subject to technical amendments
141
9.4 Electrical data for UL/cUL certification
The data given in this section must be taken into account to comply with UL/cUL certification.
Size:
230V mains
1
2
Device type:
SK 750E ...
-551-323-A
-751-323-A
-921-323-A
-112-323-A
Nominal motor power
(4-pole
standard motor)
200V [kW]
5.5
7.5
9.2
11
240V [hp]
7½
10
12.5
15
FLA [A]
[A]
22
28
35
42
Rec. mains fuse
J Class Fuse
30A
40A
50A
60A
Size:
400V mains
1
2
Device type:
SK 750E ...
-551-340-A
-751-340-A
-112-340-A
-152-340-A
-182-340-A
-222-340-A
Nominal motor
power
(4-pole
standard motor)
380V [kW]
5.5
7.5
11
15
18.5
22
460 … 480V [hp]
7½ hp
10 hp
15 hp
20 hp
25 hp
30 hp
FLA [A]
[A]
11
14
21
27
34
40
Rec. mains fuse
J Class Fuse
20A
25A
35A
50A
50A
60A